Filax 2 |
230V/50Hz | 240V/60Hz | 110V/50Hz | 120V/60Hz |
Maximum current | 16A | |||
Priority source: low voltage switching threshold | 180V | 180V | 88V | 90V |
Priority source: low voltage reverse switching threshold | 188 V | 188 V | 92 V | 94 V |
Priority source: low frequency switching threshold | 45 Hz | 46 Hz | 45 Hz | 46 Hz |
Priority source: low frequency reverse switching threshold | 47 Hz | 52 Hz | 47 Hz | 52 Hz |
Priority source: high frequency switching threshold | 60 Hz | 68 Hz | 62 Hz | 68 Hz |
Priority source: high frequency reverse switching threshold | 56 Hz | 63 Hz | 58 Hz | 63 Hz |
Priority source: maximum continuous input voltage | 260 V | 260 V | 130 V | 130 V |
Alternate source: maximum continuous input voltage | 260 V | 260 V | 130 V | 130 V |
Maximum load transfer time and reverse transfer time | 16 ms | |||
Reverse switching delay (seconds) | 30 s | |||
Operating temperature range | -20 to +50°C | |||
Humidity (non condensing) | Max 95 % | |||
LED indicators | ||||
Load supplied by priority source | Yellow | |||
Load supplied by alternate source | Yellow | |||
Priority source fault | Red | |||
ENCLOSURE | ||||
Material & Colour | ABS RAL7035 | |||
Protection category | IP 65 | |||
Weight | 0,8 kg | |||
Dimensions (h x w x d) | 120 x 255 x 75 mm | |||
STANDARDS | ||||
Safety | EN 60335-1, EN 60335-2-29 | |||
Emission / Immunity | EN55014-1, EN 55014-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-2, EN 61000-6-1 |